Type |
N/A Thermostatic Mixing Valves |
Connection Type |
N/A Barb |
Size |
N/A 1/2" |
Operating Temperature [Min] |
N/A 29 ºC85 ºF |
Operating Temperature [Max] |
N/A 54 ºC130 ºF |
Operating Pressure [Max] |
N/A 230 psi |
Flow Rate Minimum |
N/A 1 gpm (3.8L/min) |
Flow Rate Maximum |
N/A 20 gpm (76 L/min) |
Factory Set and locked |
N/A 120 ºF (49 ºC) |
Hot Temperature Supply Range |
N/A 120 - 180 ºF (48.9 - 82.2 ºC) |
Cold Temperature Supply Range |
N/A 39 - 80 ºF (3.9 - 26.7 ºC) |
Overall Length |
N/A 5.29 in134.38 mm |
Overall Height |
N/A 4.99 in126.73 mm |
C |
N/A 2.90 in73.58 mm |
Body Material |
N/A Bronze |
Seals Material |
N/A EPDM |
Springs Material |
N/A Stainless Steel |
Internal Cap Material |
N/A Brass |
Piston Material |
N/A Engineered Polymer |
Guide Tube Material |
N/A Noryl GFN2 |
Features and Benefits |
N/A Certified for distribution and point-of-use applications. Safer hot water from all outlets. Allows the water heater to be set at 140°F (60°C) or higher: Greater effective hot water volume yields less chance of Legionella within the cylinder. Every valve is tested for performance prior to shipping: Specify and install with confidence! Robust, low complexity construction: Superior reliability, improved user safety. Adjustable and lockable mechanism: Minimizes unauthorized tampering with valve setting Factory set, locked to maximum 120°F (49°C) Listed by IAPMO, CSA, and ASSE: Inspector friendly, peace of mind! |
Specification |
N/A A Temperature Actuated Mixing Valve shall be installed at single or multiple point-of-use fixtures or at the water heater to distribute tempered water throughout the domestic hot water system at a maximum temperature of 120°F (49°C). The valve shall be certified to ASSE 1017, ASSE 1069, ASSE 1070 and CSA B 125.3 standards and shall be listed by a third party. The Temperature Actuated Mixing Valve shall control the delivered water temperature via a regulating piston made from engineered polymer. The adjusting mechanism shall be protected by a lockable cover. The valve shall be a Cash Acme Heatguard® 110-D LF. |
Typical Installation |
N/A Domestic hot water distribution. To control water temperature at the source of heat (water heater) or individual/multiple point-of-use fixtures (sinks, lavatories, or bath tubs) to provide a safe distribution temperature. It can also be installed at gang shower applications where the bather has no access to the temperature adjustment means. |
Certifications |
N/A The Cash Acme Heatguard® 110-D LF is certified to ASSE 1017, ASSE 1069, ASSE 1070, CSA B125.3, and NSF 372 and listed by Iapmo, CSA, and ASSE for use in accordance with U.S and Canadian plumbing codes. |